kWh meter. energy meter. amp meter. Schleifenbauer DPM3

Kwhmeter.jpg

The Schleifenbauer DPM3 kWh meter was donated by Schleifenbauer in oct 2020. The full specs of this meter can be found at: https://www.schleifenbauer.eu/en/product-selector/dpm3/ The DPM3 has an upgradeble firmware. you can find the latest version here: https://docs.schleifenbauer.eu/?dir=Firmware

SNMP min

The MIB files are at https://docs.schleifenbauer.eu/?dir=Interfaces/SNMP -- the 244 file appears to be the most complete.

Then add these to your snmp.conf (or export a MIBS variable):

         # /etc/snmp/snmp.conf 
         mibs +SCHLEIFENBAUER-SMI
         mibs +SCHLEIFENBAUER-DATABUS-MIB
         mibs +SCHLEIFENBAUER-PRODUCTS-MIB

and you should be able to walk the data:

   snmpwalk -v 1 -c public 192.168.6.111 SdbDevInEntry

Location

The DPM3 can be found underneath the power devider panel (next to 19" cabinet)

Operation

The user manual:

Schleifenbauer-UserManual-PDU-v2.42.pdf

It's the generic Schleifenbauer manual, you can skip the parts that refer to PDUs, the interface of the DPM3 is identical to the PDU.

The DPM3 has an on board web server which can be accessed via ip-address 192.168.6.111

Measurements

It measures the following quantities on each of the 3 phases: Note: a blinking meter means that the treshold for max AMP has been surpassed. It can be reset via the web interface.

  • kWh (energy total/subtotal)
  • Amp (with peak registration)
  • Pf (power factor)
  • U (voltage)
  • W (Wattage)

it can be equiped with a Temp/Hum sensor and a dry contact output

for future reference: on 20-11-2020 the meter in the main power distribution room showed: 22270 kWh. the total of the 3 phases on the DPM3 on that date showed: 13,8(L1) + 6,4(L2) + 5,9(L3)= 26,1 kWh

Interfaces

The DPM3 supports multiple interfaces:

  • HTTP
  • API
  • Modbus
  • SNMP

So you can download the measurements at any given interval into a monitoring tool. Maybe someone feels the urge to do so... feel free to read the manual on how to set up the unit for this. Please note that, when retreiving the peak current value it is advised to reset it to zero afterwards in order to get a meaningfull value at next interval.

Access

The web interface is open to view. Only designated persons have the password to change the settings of the meter. Request for access via 'hetbestuur'. See KWh meter setup for details of the setup.



....