A "Megger" or Insulation meter [wikipedia] - can be used to measure the isolation; for example of our 3 phase motors in the Metal Mitresaw, the Circular Table Saw or any of our normal 2 phase electric machines. It helps ascertain that the device is safe to use.

It works by putting 500V or a 1000V across the measuring probes and then checking, measuring, if the resistance is well in the high mega ohms.

This means that, during measurement, there is a lethal, 1000V, across the probes !

So you must use well isolated test probes - and not hold these in your hand.


Measuring Isolation/Leakage

  1. Set the meter to 500V or 1000V.
  2. Press the orange button while nothing is connected.
  3. Check that the dial `just' moves. If not - use the back zero adjust.
  4. Release the orange button.
  5. Check that the red 'ON' LED is off.
  6. Connect the probes to the device
  7. On the machine you want to test - make sure it is as switch 'on' as is feasible (as otherwise we just test the isolation of the power cable)
  8. Connect one probe to earth and the other to one of the pins of the plug.
  9. Make sure your hands are no-where near the probes
  10. Press the orange button. Be careful, There is now a 1000V across the probes
  11. Check the resistance; it should be in the high mega ohms (note the red scale multiplier. So if you have it set to 100V; and it reads '5' you have to multiply the value by 2.
  12. Let go of the orange button
  13. Now test Earth versus the other pin.
  14. Where relevant; e.g. when the metal housing is not grounded; also measure between the housing an the pins

Typical use

It is common in workshops to test all electrical equipment once a year.

Documentation

Full manual robin-3131-manual.pdf

Service and Calibration manual robin-3131-service.pdf

History

Bought by the space early 2024

This equipment is safety category 4:

  • In-person, instructions strongly advised but not mandatory.
  • Reading, and following, the instructions on the Wiki is mandatory!

This equipment is Noise Category 3: Can be used at all hours. No limits.

Handle with care - fragile ! Handle with care.
This is a precision tool with exact dimensions and straightness.
That means: handle it gently, don't hammer on it or use it as a crowbar and so on.
(if you need a crowbar - these are wonderful for that!)


It is very important that if you accidentally drop it or think it may be out of line

  • either mark the tool very clearly...
  • or report this to the mailing list...

...so that your fellow makers do not ruin their work.